Megger MIT420/2 – Insulation and Continuity Tester

$788.00

Technical Specs

Megger MIT420/2 - Insulation and Continuity Tester Specs

Insulation Nominal test voltages 50 V, 100 V, 250 V, 500 V, 1000 V
Insulation resistance range 200 GΩ
Range Full Scale Accuracy 1000 volts ±3% ±2 digits ±0.2% per GΩ   500 volts ±3% ±2 digits ±0.4% per GΩ   250 volts ±3% ±2 digits ±0.8% per GΩ   100 volts ±3% ±2 digits ±2.0% per GΩ   50 volts ±3% ±2 digits ±4.0% per GΩ
Analog range 1 GΩ full scale
Short Circuit Current 2 mA +0% -50%
Terminal voltage -0% +20% ±1 V
Test Current on load 1 mA at min. pass value of insulation specified in BS7671, HD384and IEC364, 2 mA max.
EN61557 Operating range 0.10 M½ to 1.00 GΩ
Leakage Current 10% ±3 digits
Voltage display 3% ±3 digits ±0.5% of rated voltage
Polarization Index (PI) 10 min/1 minute ratio
Dielectric Absorption Ratio (DAR) 60 sec/30 sec ratio
Notes (1) All ranges measure from 0.00 M½ upwards.   (2) Above specifications only apply when high quality silicone leadsare being used.
Measurement 0.01 ½ to 99.9 ½ (0 to 100 ½ on analog scale)
Accuracy ±3% ±2 digits (0 to 100 Ω)
Open circuit voltage 5 V ±1 V
Test current 200 mA (–0 mA +20 mA)   (0.01 ½ to 9.99 Ω)   20mA (±1 mA )   (10.0 ½ to 99.9 Ω)
Zero offset at probe tips 0.10Ω typical
Lead resistance zeroing Up to 9.00 Ω
Buzzer Variable limit 1Ω, 2Ω, 5Ω,10Ω, 20Ω
Measurement 0.01 kΩ to 1000 kΩ   (0 to 1 MΩ on analog scale)
Accuracy ±3% ±2 digits   Open circuit voltage 5 V ±1 V   Short circuit current 20 µA ± 5 µA
Voltage range 0 to 600 V d.c. ±2% ±2 digits   10 mV to 600 V TRMS sinusoidal (40 to 400 Hz) ±2% ±2 digits   0 to 1000 V on Analog scale   Unspecified input level 0 - 10 mV (40 to 400 Hz)      For non-sinusoidal waveforms additional specification apply:   ±3% ±2 digits 101 mV to 600 V TRMS and ±8% ±2 digits 10 mV to 100 mV TRMS
Measurement range 100 pF to 10 µF
Accuracy ± 5.0% ±2 digits
Default Voltmeter Operates at >25 V a.c. or d.c. on any range except OFF
Frequency 40 - 450 Hz (40 Hz - 99.9 Hz)   ±0.5% ±1 digit (100 Hz to450 Hz)
Capacity >1000 test results
Download Bluetooth wireless
Bluetooth Class Class II
Range up to 10 m
Power Supply 5 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline NiMH rechargeable cells may be used.   Battery life: 2200 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ
Instrument 220 x 92 x 50 mm (8.66 in. x 3.63 in. x 1.97 in.)
Instrument and case 456 x 178 x 89 mm (18 in. x 7 in. x 3.5 in.)
Instrument only 590 gms (20.73 oz.), 775 gms (27.22 oz.) with boot
Instrument and case 1.75kg (3.86 lb)
Fuse Use only a 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse of highbreaking capacity HBC 50 kA minimum. Glass fuses MUST NOT be fitted.
Safety Protection The instruments meet EN 61010-1 (1995) to 600 V phase to earth, Category IV. Refer to safety warnings supplied.
E.M.C. In accordance with IEC 61326 including amendment No.1
Temperature coefficient <0.1Ω per °C up to 1 GΩ
Operating range -10 to +55° C
Operating humidity 90% RH at 40° C max.
Storage temperature range -25 to +70° C
Calibration Temperature +20° C
Maximum altitude 2000 m
Dust and water protection IP54 Protected against dust and splashing water
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “Megger MIT420/2 – Insulation and Continuity Tester”
SKU: Megger-MIT420-2 Category: Brand: