Fluke 1746/B/EUS Three-Phase Power Quality Loggers

$5,486.00

Technical Specs

Fluke 1746/B/EUS Three-Phase Power Quality Loggers Specs

Parameter Range
Voltage 1000 V
Current: Direct input i17xx-flex 1500IP 24 1500 A
1500 A 0.1 A
i17xx-flex 3000IP 24 3000 A 300 A
3000 A 0.1 A
i17xx-flex 6000IP 36 6000 A 600 A
6000 A 0.1 A
i40s-EL clamp 4 A
40 A 10 mA
Frequency 42.5 Hz to 69 Hz
Auxiliary input ±10 V dc
Voltage min/max 1000 V
Current min/max Defined by accessory
THD on voltage 1000%
THD on current 1000%
Voltage harmonics 2nd to 50th 1000 V
Current harmonics 2nd to 50th Defined by accessory
Flicker PLT, PST 0 to 20
Parameter Influence quantity
150 A / 1500 A 300 A / 3000 A
Active Power P PF ≥ 0.99
Apparent power S PF ≥ 0.99
Reactive power Q 0 ≤ PF ≤ 1
Reactive power Q 0 ≤ PF ≤ 1
Power Factor PF -
Additional uncertainty in% of range VP-N>250 V
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
Power consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ± 15 %
Battery Li-ion 3.7 V, 9.2 Wh, customer-replaceable
On-battery runtime Typically 4 hours
Charging time < 6 hours
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-φ, 1-φ IT, split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC 61000-4-30 Aux, Power: 200 ms)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging interval 10 min for all parameters   2 hrs (long term Flicker PLT)   150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual harmonics 2nd to 50th harmonic   Grouping according to IEC 61000-4-7 user configurable depending on application:   Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics 1st to the 50th interharmonic
Total harmonic distortion Calculated on 50 voltage harmonics
Events Voltage: dips, swells, interruptions, current: inrush current   1748: mains signaling, transients (low frequency)
Triggered recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s   (URMS1/2 according to IEC 61000-4-30)   Waveform of voltage and current up to 200 ms, 10/12 cycles   Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
Inrush RMS profile based on 1/2 cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains signaling Two user defined frequencies up to 3 kHz
PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160 Compliance with standard
Programmable PQ limits Enables user defined limits for local standards compliance
Harmonics IEC 61000-4-7: Class 1
Power quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power quality compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2   Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V   Power Supply: Overvoltage Category IV, Pollution Degree 2   Li-ion Battery: IEC 62133
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect ® 3000 series modules   (requires supported USB to BLE or WiFi/BLE adapter, check for availability)
USB-mini-B Data download device to PC
Number of inputs 4 (3 phases referenced to neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Number of inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8   Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24"   3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24"   6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36"   40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Number of inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Number of inputs 2
Supported modules Fluke Connect ® 3000 series
Acquisition 1 reading/s
Operating temperature -25 °C to +50 °C (-13 °F to 122 °F)1
Storage temperature Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidity IEC 60721-3-3: 3K6:   -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %   40 °C (104 °F): 55 %   50 °C (122 °F): 35 %
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IEC 60529: IP50   IEC 60529: IP65 with IP65 rated voltage connector
Vibration IEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A   IEC 61000-6-5 Power station environment   Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)   USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Features 1742
Voltage, current, power, power factor, frequency •
Energy forward/reverse •
Peak Demand •
THD •
Flicker •
Voltage and current harmonics (to 50th)1 •
Unbalance1 •
Rapid voltage change events1 •
Interharmonics (to 50th)1 •
Dips, swells, interruption and transient events tables1 •
Inrush current1 •
Transients (low frequency)/Waveform deviation events2 •
Trend •
Waveform snapshots2 •
RMS profile2 •
Ethernet •
USB (mini B) •
WiFi download Instrument to device •
Wifi download via WiFi hub (requires registration) Opt.
Flexible current probe not /B version
USB stick •
USB cable •
3PHVL-1730 3-Phase + neutral voltage test lead •
Test lead set red/black 0.18 m •