TSI AVM440 Velometer Thermal Anemometer Specs
| Range (AVM410) | 0 to 4,000 ft/min (0 to 20 m/s) |
| Range (AVM430, AVM440) | 0 to 6,000 ft/min (0 to 30 m/s) |
| Accuracy (AVM410) | ±5% of reading or ±5 ft/min (±0.025 m/s), whichever is greater |
| Accuracy (AVM430, AVM440) | ±3% of reading or ±3 ft/min (±0.015 m/s), whichever is greater |
| Resolution | 1 ft/min (0.01 m/s) |
| Dimensions | 1 to 250 inches in increments of 0.1 in. (1 to 635 cm in increments of 0.1 cm) |
| Range | Actual range is a function of velocity, and duct size |
| Range (AVM410, AVM430) | 0 to 200°F (-18 to 93°C) |
| Range (AVM440) | 14 to 140°F (-10 to 60°C) |
| Accuracy | ±0.5°F (±0.3°C) |
| Resolution | 0.1°F (0.1°C) |
| Range | 0 to 95% RH |
| Accuracy | ±3% RH |
| Resolution | 0.1% RH |
| Range | 40 to 140°F (5 to 60°C) |
| Resolution | 0.1°F (0.1°C) |
| Range | 5 to 120°F (-15 to 49°C) |
| Resolution | 0.1°F (0.1°C) |
| Operating (Electronics) | 40 to 113°F (5 to 45°C) |
| Model AVM410, AVM430 Operating (Probe) | 0 to 200°F (-18 to 93°C) |
| Model AVM440 Operating (Probe) | 14 to 140°F (-10 to 60°C) |
| Storage | -4 to 140°F (-20 to 60°C) |
| Range | 12,700+ samples and 100 test IDs |
| Probe Length | 40 in. (101.6 cm) |
| Probe Diameter of Tip | 0.28 in. (7.0 mm) |
| Probe Diameter of Base | 0.51 in. (13.0 mm) |
| Articulating Section Length | 7.8 in. (19.7 cm) |
| Diameter of Articulating Knuckle | 0.38 in. (9.5 mm) |